Insulation R-Value
Add up a wall’s R-value layer by layer, and compare its heat loss with a greenhouse covering.
A wall’s R-value is the sum of its layers: each material’s R-value per inch times its thickness, plus fixed values for thin layers and the air films on each surface. The U-value is 1 divided by the total R, and the heat lost through the wall is U times the area times the temperature difference. Louisiana’s state energy office adds a wall of drywall, R-11 batts, foam board, an air space and brick to R-18.17 this way.
How the calculation works
Adding the layers. Louisiana’s wall worksheets add each layer’s R-value, starting with an inside air film of 0.68 and ending with an outside film of 0.17. A material with an R-value per inch counts as that figure times its thickness; thin layers such as ½-inch gypsum board (0.45) and an air space (0.97) count at fixed values; a product counts at the R-value on its label. Where a source gives a range per inch, the tool carries the range through to the total.
U-value and heat loss. The U-value is 1 ÷ total R, in BTU per hour, square foot and °F; the University of Alaska Fairbanks describes R as the inverse of U. The heat lost through the wall is U × area × (inside − outside), the form ASAE EP406.4 uses for greenhouse coverings.
The comparison. Greenhouse coverings come from ASAE EP406.4 Table 1, the same values as the greenhouse heating cost calculator; masonry and framed walls come from the University of Alaska Fairbanks’ Table 1, adapted from the Northeast handbook Greenhouses for Homeowners and Gardeners (NRAES-137). Both are U-values for the whole assembly, surfaces included, so the tool compares them with your wall’s total, air films and all.
R-value per inch, by source
| Material | R per inch | Source |
|---|---|---|
| Fiberglass, batts or blown | 2.2 to 3.2 | Louisiana |
| Fiberglass, batt or board | 2.5 to 4 | PNNL |
| High-density fiberglass batts | 3.2 to 3.5 | Louisiana |
| Rock wool batts | 2.8 to 3.7 | Louisiana |
| Mineral wool rigid board | 3 to 4 | PNNL |
| Cellulose, loose blown | 2.8 to 3.8 | Louisiana |
| Expanded polystyrene (EPS) | 3.8 to 4.4 | PNNL; US DOE |
| Extruded polystyrene (XPS) | 5 | PNNL; US DOE |
| Polyisocyanurate board | about 6; 6.5 | PNNL; US DOE |
| Spray foam, closed-cell or high-density | about 6; 6.5 | PNNL; US DOE |
| Spray foam, open-cell | about 3.6 | US DOE (R-12.6 at 3.5 in; our division) |
| Rigid foam boards, all kinds | 3.6 to 7.5 | Louisiana |
| Perlite, concrete block fill | 2.5 to 4.0 | Louisiana |
| Vermiculite, concrete block fill | 2.4 to 3.0 | Louisiana |
| Plywood; softwoods | 1.25 | Louisiana |
| Wood siding | 0.79 | Louisiana |
| Brick | 0.20 | Louisiana |
| Concrete | 0.08 | Louisiana |
PNNL’s Building America Solution Center (updated 2021) and US DOE’s Guide to Home Insulation (2010) differ on polyisocyanurate and closed-cell foam; the tool carries both as a range. Where a product is labeled, its label is the figure to use.
Whole walls and coverings
| Assembly | U-value | R (1 ÷ U) | Source |
|---|---|---|---|
| Single glass or single film | 1.1 | 0.91 | ASAE |
| Double polyethylene | 0.70 | 1.43 | ASAE |
| Double polyethylene, IR inhibited | 0.50 | 2.0 | ASAE |
| Polycarbonate, double-wall | 0.56 to 0.63 | 1.59 to 1.79 | ASAE |
| Double polyethylene, thermal blanket closed | 0.44 | 2.27 | ASAE |
| Concrete block, 8 inches | 0.5 | 2.0 | UAF (NRAES-137) |
| Concrete block, 8 inches, with 2 inches of foamed polystyrene board | 0.10 | 10 | UAF (NRAES-137) |
| Concrete block, 8 inches, with 2 inches of foamed urethane board | 0.07 | 14.3 | UAF (NRAES-137) |
| Wood-framed wall with 1.5 inches of urethane board | 0.12 | 8.3 | UAF (NRAES-137) |
U in BTU per hour, square foot and °F. R is our arithmetic. UAF’s table gives coverings somewhat higher U-values than ASAE: 1.2 for single glass, 1.25 for single film and 0.8 for double film. This tool uses ASAE’s values for coverings, as the greenhouse heating cost calculator does.
What it does not do
- It treats every layer as continuous. Studs, fasteners and gaps carry heat around the insulation, so a framed wall loses more than its layer total suggests; the sources here give no correction.
- Its per-inch figures are ranges from general tables. Loose and fibrous materials vary with how densely they are packed.
- It does not count heat lost through the floor, the ground or the perimeter, or by air leaking through the wall.
- It does not judge whether a wall is insulated enough for a use, and gives no costs.
Sources
- Louisiana Department of Natural Resources, Technology Assessment Division. R-values of materials and wall worksheets. Energy-efficient construction education pages; archived copy of 19 April 2024 (the original address now redirects). R per inch, fixed values, air films and the worked walls.
- Pacific Northwest National Laboratory. Updated 23 December 2021. Typical R-Values and Vapor Retarder Classifications of Common Insulation Materials. Building America Solution Center, US Department of Energy.
- US Department of Energy. October 2010. Guide to Home Insulation, DOE/EE-0340. The R-values in its cost table: spray foams, foam boards and batts.
- American Society of Agricultural Engineers. 2003. ANSI/ASAE EP406.4, Heating, Ventilating and Cooling Greenhouses. Equation 1 and Table 1 (U-values of coverings, with and without a thermal blanket).
- University of Alaska Fairbanks Cooperative Extension Service. Revised July 2024. Controlling the Greenhouse Environment, HGA-00336. R as the inverse of U, and Table 1 of heat transfer coefficients, from Greenhouses for Homeowners and Gardeners (NRAES-137).
CC BY 4.0. Cite as "Open Agriculture Technology Insulation R-Value Calculator (openagriculturetechnology.com)".
Frequently asked questions.
How do I calculate the R-value of a wall?
Add the R-values of every layer, from the inside air film to the outside one. Louisiana’s worksheet wall adds an inside air film (0.68), ½-inch drywall (0.45), 3½-inch batts (11.00), ¾-inch foam board (4.00), an air space (0.97), brick (0.90) and an outside air film (0.17) to R-18.17. A material rated per inch counts as its figure times its thickness.
What is the R-value per inch of rigid foam insulation?
Expanded polystyrene (EPS) 3.8 to 4.4, extruded polystyrene (XPS) 5, and polyisocyanurate about 6, according to PNNL’s Building America Solution Center (2021). US DOE’s Guide to Home Insulation (2010) gives the same EPS and XPS figures and 6.5 for 1 inch of polyisocyanurate.
What is the R-value of fiberglass insulation per inch?
Louisiana’s table gives 2.2 to 3.2 for fiberglass batts or blown fiberglass and 3.2 to 3.5 for high-density batts; PNNL gives 2.5 to 4 for fiberglass batt or board. A labeled batt is rated at its label: the 3½-inch batts in Louisiana’s worksheet count as R-11.
What is the R-value of spray foam insulation per inch?
US DOE’s Guide to Home Insulation (2010) lists closed-cell polyurethane spray foam at R-6.5 for 1 inch and open-cell at R-12.6 for 3.5 inches, about 3.6 per inch (our arithmetic). PNNL gives high-density spray foam about 6 per inch.
What is the R-value of a greenhouse covering?
R is 1 divided by the U-value. With ASAE EP406.4’s U-values, single glass or single film (1.1) is about R-0.91, double polyethylene (0.70) about R-1.43, IR-inhibited double polyethylene (0.50) R-2.0, and double-wall polycarbonate (0.56 to 0.63) about R-1.6 to 1.8 (R ours). These include the surfaces, so add no air films to them.
How do I convert a U-value to an R-value?
Divide 1 by it: the University of Alaska Fairbanks describes R as the inverse of U. In US units, U is in BTU per hour, square foot and °F and R in hour, square foot and °F per BTU, so a U of 0.10 is R-10.
How much heat does an insulated knee wall save in a greenhouse?
Compare the U-values. With 100 sq ft at a 50°F difference, double polyethylene (U 0.70, ASAE) loses 3,500 BTU an hour, and an 8-inch concrete block wall with 2 inches of foamed polystyrene board (U 0.10, UAF from NRAES-137) loses 500, a seventh as much (our arithmetic).
Why does an R-value calculation include air films?
The surfaces of a wall add resistance of their own, and Louisiana’s worksheets count them: 0.68 on the inside surface and 0.17 on the outside. For a thin wall they are a large share of the total; for a thick one they matter little. Coverings’ U-values from ASAE already include them.